Hardware
The TC Compact Series consists of the following
major components:
Input/Output Points
Power Supply
Input/Output Points
Controller Processor
The TC Compact input/output points perform A/D
or D/A conversion, signal processing, point
command output, and communication with the
controller processor. The terminal blocks are
removable for easy termination of field wiring.
The Universal and Super Universal points
leverage TX-I/O™ Technology from Siemens
Building Technologies to configure an extensive
variety of point types.
0-10V input
Universal Input (UI) and Universal Input/Output
(U) points are software-selectable to be:
4-20 mA input
Digital Input
Pulse Accumulator inputs
1K Ni RTD @ 32°F (Siemens, Johnson
Controls, DIN Standard)
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Thermistor (Type 2 and Type 3) @
77°F
100K NTC Thermistor (Type 2) @ 77°F
0-10V Analog Output (Universal Input/Output
(U) points only)
Super Universal (X) points (TC-24 and TC
0-10V input
-36
only) are software-selectable to be:
4-20 mA input
Digital Input
Pulse Accumulator inputs
1K Ni RTD @ 32°F (Siemens, Johnson
Controls, DIN Standard)
1K Pt RTD (375 or 385 alpha) @ 32°F
10K NTC Thermistor (Type 2 and Type 3) @
77°F
100K NTC Thermistor (Type 2) @ 77°F
0-10V Analog Output
4-20 mA Analog Output
Digital Output (using external relay)
Dedicated Digital Input (DI) points (TC-16 only)
are dry contact status sensing.
Digital Output (DO) points are 110/220V 4 Amp
(resistive) Form C relays; LEDs indicate the status
of each point.
All TC Compact Series models support 0-10 Vdc
Analog Output circuits.
On TC-24 and TC
Power Supply
-36 models, the Super Universal
points may be defined as either 0-10 Vdc or 4-20
mA Analog Output circuits.
The 24 volt DC power supply provides regulated
power to the input/output points and active
sensors. The power supply is internal to the TC
Compact housing, eliminating the need for
external power supply and simplifying installation
and troubleshooting.
The power supply works with the processor to
ensure smooth power up and power down
sequences for the equipment controlled by the I/O
points, even through brownout conditions.