December 2001 User’s Manual 2000585-001 Siemens Applied AutomationSiemens Applied AutomationSiemens Applied AutomationSiemens Applied Automation
2 •••• Introduction 2000585-001 Overview, Continued The Advance DataNET Hub (DNH) is available in three package configu-rations: • 19-inch Rack U
2000585-001 Introduction •••• 3 Overview, Continued A network of DataNET hubs forms a tree-like hierarchy. A DNH may connect to as many as eight “
4 •••• Introduction 2000585-001 DataNET Hub Operation Figure 1-4 shows the individual links that connect three DataNET hubs and several end devices
2000585-001 Introduction •••• 5 DataNET Hub Operation, Continued DataNET switching operates by dynamically and automatically learning the topology
6 •••• Introduction 2000585-001 DataNET Hub Specifications Dimensions Rack Mounted Package Configuration See Figure 1-5 for Outline Drawing and
2000585-001 Introduction •••• 7 DataNET Hub Specifications, Continued Ambient Installation Conditions Operation: -18° to +50°C (0° to 122°F) 0-99%
8 •••• Introduction 2000585-001 DataNET Hub Specifications, Continued DataNET Option, Standard Cable • Cable connection by Belden 9182 (single p
2000585-001 Introduction •••• 9 DataNET Hub Specifications, Continued The Table below compares key communication features between using Advance Da
10 • Introduction 2000585-001 DataNET Hub Specifications, Continued Figure 1-3 Description U.S. Inches Metric mm A Rack Height 6.97 177
2000585-001 Introduction • 11 DataNET Hub Specifications, Continued Figure 1-4 Description U.S. Inches Metric mm A Wall Width 17.48 444 B W
Copyright Notice 2000 by Siemens Applied Automation Bartlesville, Oklahoma, 74003, U.S.A. All rights reserved. This publication is for information o
12 •••• Introduction 2000585-001 DataNET Hub Specifications, Continued PKLMNOc/lSTTOPK0Pc/lRBOTTOMCQLEFTGHIJc/lQRIGHTDAEFFRONTB Figure 1-7 Des
2000585-001 Introduction •••• 13 DataNET Hub Specifications, Continued L Spacing from wall to front cable entry hole (top and bottom) 127 5 M
2000585-001 Installation •••• 15 Chapter 2 Installation Overview This chapter is intended for installation personnel. After completing the procedur
16 •••• Installation 2000585-001 Unpacking and Inspection This section provides the steps to follow when receiving and unpacking the Advance DataNE
2000585-001 Installation •••• 17 Wall or Rack Mounting Installation The Advance DataNET Hub should be: • Installed in a location that is free from
18 •••• Installation 2000585-001 Wall or Rack Mounting Installation, Continued The DNH rack mount configuration is designed for a standard 19-inch
2000585-001 Installation •••• 19 Site Wiring Requirements How you wire to the DNH is dependent upon the site requirements: • CE (Conformite Europe
20 •••• Installation 2000585-001 Site Wiring Requirements, Continued The DataNET channel connections can be either copper wire or fiber optic cabl
2000585-001 Installation •••• 21 Site Wiring Requirements, Continued The following information pertains when using copper wire See Page 23, CE Ins
2000585-001 Table of Contents • i Table of Contents Preface iii Technical Support iv Safety Practices and Precautions v Introduction 1 Overview
22 •••• Installation 2000585-001 Site Wiring Requirements, Continued Use Cable Gland wiring method. Each cable gland allows entry of one duplex fi
2000585-001 Installation •••• 23 CE Installations This section should be used for installation sites that must conform to CE (Conformite Europeene)
24 •••• Installation 2000585-001 CE Installations, Continued 3. A split ferrite filter must be clamped to DataNET copper wire and fixed immediate
2000585-001 Installation •••• 25 Wiring Connections Two removable access plates provide power and I/O entry through the underside of the DNH. The p
26 •••• Installation 2000585-001 AC Power (Mains) Connections Each of the DNH electronic modules has a Power Supply Assembly lo-cated below the Dat
2000585-001 Installation •••• 27 AC Power (Mains) Connections, Continued Step Action 3. Install 15-Ampere circuit breakers, disconnect switches
28 •••• Installation 2000585-001 AC Power (Mains) Connections, Continued Step Action 7. Plug the connector back into its base and secure the tw
2000585-001 Installation •••• 29 DataNET Copper Connections The DNH consist of two identical hubs in one enclosure. The left side is usually the Da
30 •••• Installation 2000585-001 DataNET Copper Connections, Continued See Figure 2-1. Each DataNET Hub board has nine DataNET ports. One of the D
2000585-001 Installation •••• 31 DataNET Copper Connections, Continued Behind each single port connector is an associated jumper pin block, see Fi
ii •••• Table of Contents 2000585-001 Table of Contents, Continued Command Summary 69 Command Descriptions 69 Parts Catalog 85 Introduction 85
32 •••• Installation 2000585-001 DataNET Copper Connections, Continued Step Action 1. Plug the DataNET Hub Signal Equalizer Board into the se-l
2000585-001 Installation •••• 33 DataNET Copper Connections, Continued Each of the four downlink connectors (TB15, TB16, TB17, TB18) contain wring
34 •••• Installation 2000585-001 DataNET Hub Signal Equalizer Board This section sets the switches on the DataNET Hub Signal Equalizer board. This
2000585-001 Installation •••• 35 DataNET Hub Signal Equalizer Board, Continued When cable lengths are unknown, or the cable is other than the rec
36 •••• Installation 2000585-001 DataNET Hub Signal Equalizer Board, Continued Selec-tion Ratio DB loss SW1 SW2 SW3 1 2 3 1 2 3 1 2
2000585-001 Installation •••• 37 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths This section is used to set the swi
38 •••• Installation 2000585-001 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued Signals are viewed with a
2000585-001 Installation •••• 39 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued This procedure is for de
40 •••• Installation 2000585-001 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued Step Action 3. Examine
2000585-001 Installation •••• 41 Signal Equalizer Settings for Non Recommended Cable or Unknown Cable Lengths, Continued Step Action 3. cont. The
2000585-001 Preface •••• iii Preface This manual is intended to introduce users to the Advance DataNET Hub (DNH). It includes complete instruction
42 •••• Installation 2000585-001 DataNET Fiber Optic Connections All DataNET Fiber Optic uplink and downlink port connections are made through the
2000585-001 Installation •••• 43 DataNET Fiber Optic Connections Duplex Fiber, 62.5/125 micron 1. Plug the DataNET Fiber Optic Coupler board in
2000585-001 Installation •••• 45 Ethernet Connections The DNH consists of two identical hub modules in one enclosure. The left side is usually th
46 •••• Installation 2000585-001 Ethernet Connections, Continued 1. The 10BASET data cable requires a minimum of two twisted pairs (transmit pair
2000585-001 Data Communications Setup •••• 47 Chapter 3 Data Communications Setup Introduction This chapter provides maintenance personnel instruc
48 •••• Data Communications Setup 2000585-001 Introduction, Continued This chapter provides the following information: Topic Page Configuring Your
2000585-001 Data Communications Setup •••• 49 Configuring Your PC The Advance DataNET Hub (DNH) has a built-in utility for configuring its operati
58 • Data Communications Setup 2000585-001 Setting Network Address, Continued See Assigning an IP Address, page 59 to learn how to assign an IP Ad
2000585-001 Data Communications Setup •••• 51 Configuring Your PC, Continued 8. Scroll each field and select the following Port Settings: Bits p
iv •••• Preface 2000585-001 Technical Support At Siemens Applied Automation we take pride in the on going support we provide our customers. When yo
52 •••• Data Communications Setup 2000585-001 Configuring Your PC, Continued 13. Click Terminal Settings button. The Terminal Settings dialog box
2000585-001 Data Communications Setup •••• 53 Configuring Your PC, Continued 16. Click OK to return to main menu. 17. From the Main menu select
54 •••• Data Communications Setup 2000585-001 Establishing a Connection Once your PC is set up, as described in Configuring Your PC, you are ready
2000585-001 Data Communications Setup •••• 55 Establishing a Connection, Continued A password name can consist of any combination of alphanumeric
56 •••• Data Communications Setup 2000585-001 Establishing a Connection, Continued 3. At the >>>> prompt type: login password and pres
2000585-001 Data Communications Setup •••• 57 Setting Network Address This section provides instructions to configure an Advance DataNET ‘A’ or ‘
58 • Data Communications Setup 2000585-001 Setting Network Address, Continued See Assigning an IP Address, page 59 to learn how to assign an IP Ad
2000585-001 Data Communications Setup •••• 59 Assigning an IP Address Each individual hub board (“hub-half”) in the system must have a unique IP
60 •••• Data Communications Setup 2000585-001 Firmware Updates Periodically we will provide our users with firmware upgrades. Perform the following
2000585-001 Data Communications Setup • 61 Firmware Updates, Continued 6. Click on Send Text File. The Send Text File dialog box will appear. In
2000585-001 Safety Practices and Precautions •••• v Safety Practices and Precautions This product has been designed and tested in accordance with
62 •••• Data Communications Setup 2000585-001 System Status LEDs The Advance DataNET Hub Communication boards have status LEDs for monitoring the D
2000585-001 Data Communications Setup •••• 63 System Status LEDs, Continued The yellow (WARN) blink codes are shown below. The yellow (WARN) stat
64 • Data Communications Setup 2000585-001 System Status LEDs, Continued There are four Ethernet Link Status LEDs. Link Active LED is Green (on
2000585-001 Data Communications Setup •••• 65 Troubleshooting This chapter is intended for maintenance personnel. Failure of the DNH to establish
66 •••• Data Communications Setup 2000585-001 Troubleshooting, Continued The device may have an invalid or duplicate device ID, IP address, Sub-ne
2000585-001 Data Communications Setup •••• 67 Troubleshooting, Continued If a DNH port green LED is off, or intermittently flashes between green
68 •••• Data Communications Setup 2000585-001 Troubleshooting, Continued 12. At the >>>> prompt type: test off Test off places the se
2000585-001 Command Summary •••• 69 Chapter 4 Command Summary Command Descriptions This chapter is intended for maintenance personnel. This chapte
70 •••• Command Summary 2000585-001 Command Descriptions, Continued list nnn, xxx List xxx events, starting with number nnn list on Continuously
2000585-001 Command Summary •••• 71 Command Descriptions, Continued This command configures the hub-half IP address. Each individual hub board (“
vi •••• Safety Practices and Precautions 2000585-001 Safety Practices and Precautions, Continued Before switching on the power, check that the ope
72 •••• Command Summary 2000585-001 Command Descriptions, Continued This command sets the address of the IP router to which the hub-half should se
2000585-001 Command Summary •••• 73 Command Descriptions, Continued This command deletes selected items from the hub’s Source Address Table (SAT)
74 •••• Command Summary 2000585-001 Command Descriptions, Continued This command displays the hub-half’s link state table. The link state table in
2000585-001 Command Summary •••• 75 Command Descriptions, Continued 5. After you have selected the “hub_rom.mot” file and click on “OK,” HyperTe
76 •••• Command Summary 2000585-001 Command Descriptions, Continued dn window Displays the transmit “window” for the HDLC protocol used by DataNET
2000585-001 Command Summary •••• 77 Command Descriptions, Continued dn portdelay timeSets the “port delay” parameter to the value given, in milli
78 •••• Command Summary 2000585-001 Command Description, Continued This command generates a simple list of available commands. Enter the list com
2000585-001 Command Summary •••• 79 Command Description, Continued The event display gives a time-stamp, and an event description. All events oth
80 •••• Command Summary 2000585-001 Command Descriptions, Continued This command logs the user out of a session. The user must be logged out of th
2000585-001 Command Summary •••• 81 Command Descriptions, Continued This command places a selected port into a hardware diagnostic mode. The comm
2000585-001 Introduction •••• 1 Chapter 1 Introduction Overview The Advance DataNET Hub (DNH) functions as a communication router on an Advance Com
82 •••• Command Summary 2000585-001 Command Descriptions, Continued The trace command controls the hub’s frame tracing function. This fea-ture cap
2000585-001 Command Summary •••• 83 Command Descriptions, Continued sets up tracing on downstream port 2, for input data only. trace crosslink ou
84 •••• Command Summary 2000585-001 Command Descriptions, Continued This command controls the event buffer display’s “verbose” mode. When verbose
2000585-001 Parts Catalog •••• 85 Chapter 5 Parts Catalog Introduction This chapter is intended for maintenance personnel. The Chapter provides a
86 •••• Parts Catalog 2000585-001 Available Parts The available DNH assemblies and parts, with their applicable part num-ber are shown below. Part
2000585-001 Parts Catalog •••• 87 Available Parts, Continued Part Description Ordering Number Cable, fiber optic patch, 3 meter, MM 62.5/125; 2
Siemens Applied Automation 500 West Highway 60, Bartlesville, OK 74003 Phone 918-662-7000, Fax 918-662-7052