6
Function (continued)
Industrial Wireless Communication
IWLAN – Client Modules IEEE 802.11n
Overview
iFeatures (only in conjunction with KEY-PLUG or
SCALANCE W722-1 RJ45))
iPCF (industrial Point Coordination Function):
The iPCF mode is a good choice for applications with require-
ments for real-time and predictable response times (determinis-
tic response), even when mobile nodes are roaming from
one access point to the next. This ensures that wireless
PROFINET IO is supported and that safety-related signals,
e.g. emergency stop, can be linked into the RF field.
The iPCF mechanism expands the IEEE 802.11 standard and
must be available on both the client module and the access
point. In an RF field in which iPCF is used, no IEEE 802.11-com-
pliant nodes can be operated.
iPCF is recommended for applications where wireless network
nodes move along predefined paths (e.g. suspended monorail).
RCoax radiating cables or directional antennas must be used for
this purpose.
Linking in an automated guided vehicle system using iPCF with the SCALANCE W722-1 RJ45
iPCF-MC (iPCF Management Channel)
1)
:
iPCF-MC is available as a further development of iPCF.
This mode should be used if IWLAN stations that also support
iPCF-MC move freely about in the coverage area (especially
when using omni-directional antennas) and are to exchange
data deterministically. This functionality can only be achieved in
connection with access points with two wireless interfaces and
the KEY PLUG.
Note:
These iFeatures cannot be used in parallel.
Diagnostics and management
Web-based (HTTP/HTTPS) management tool for configuration
and diagnostics using a standard browser
LEDs for signaling operating status and fault/error states
Signaling of faults by means of SNMP trap or e-mail to a
network management tool
Configuration and diagnostics using Web based
Management, Command Line Interface, and SNMP. Devices
and networks can be configured using STEP 7 (TIA Portal).
For cyclic monitoring, diagnostics and documentation
(reporting) in network mode, the SINEMA Server software is
recommended.
1)
Available soon
RCoax Cable Segment 1 RCoax Cable Segment 2
Access Point
SCALANCE
W784-1RR in
the cabinet
Access Point
SCALANCE
W784-1RR in
the cabinet
G_IK10_XX_30172
IWLAN RCoax Cable IWLAN RCoax Cable
Client Module
SCALANCE
W722-1 RJ45
Panel PC
Client Module
SCALANCE
W722-1 RJ45
Panel PC
Client Module
SCALANCE
W722-1 RJ45
Panel PC
WinAC WinACWinAC
Kap_06_IWC_en.book Seite 94 Dienstag, 7. Oktober 2014 1:47 13