4 Communication settings and guide of HMI connecting with controller
Internal Output
R 0000-FFFF
------ HHHH
Data Area
M 0000-FFFF
------ HHHH
First CPU Link
L 00000-03FFF
------ HHHHH
Second CPU Link
L 10000-FFFFF
------ HHHHH
On Delay Timer
TD 00000-65535
------ DDDDD
External Input
------ WX 000.00-05A.09 HHH.DD Read Only
External Output
------ WY 000.00-05A.09 HHH.DD
Remote Input
------ WX 100.00-9FF.09 HHH.DD Read Only
Remote Output
------ WY 100.00-9FF.09 HHH.DD
Word Internal Output
------ WR 0000-C3FF HHHH
Special Word Output
------ WRF 000-FFFF HHHH
Data Area
------ WM 0000- FFFF HHHH
First CPU Link
------ WL 0000-03FF HHHH
Second CPU Link
------ WL 1000-FFFF HHHH
Timer Counter
------
TC 00000-65535 DDDDD
NoteX0.015 in the HMI match x15 in the PLC,Y1.000 in the HMI match Y100,WX0.09 in the HMI
match WX9 in the Plicate effective address is deleted radix point and the first zero behind radix point.
The list of address correspondence
Bit Address
Word Address
PLC address
Notes
X 00.000-00.047
X 0000-0047
Y 01.000-01.031
Y 0100-0131
WX 000.00-000.03 WX 0000-0003
WY 001.00-Y001.01 WY 0010-0011
Note: The range of X, Y, WX, WY is according to the I/O assign. Make sure the I/O address before using
the register.
Note:
1. Communication setting
EH series, only port1 supports procedure 2.Switch DIP and change special Internal Input (WR) value to
select procedure.
EH150 series
only EHCPU***A/448/516/548 support procedure 2.
EH PLC connect with PC only by procedure 1.
2. CPU related actions
EH150
DIP 5 must be set on.
If DIP 5 is on, which procedure (1 or2) to use by judging the value of the WR F037.The highest bit of
WR F037 must be on, so that the other bits can be written in. The data keep on, when turn on the power
again.
o By entering 0x8000, turn on the power again and value of the address is 0x0000.After settings,
communication with procedure 1.
o By entering 0xC000, turn on the power again and value of the address is 0x4000.After settings,
communication with procedure 2.
- 111 -