4 Communication settings and guide of HMI connecting with controller
(1) Setting ID of Profibus by switching 8-bit Dip(DIP1 is lowest bit, DIP8 is highest bit),range is from 3
to 125;
ID must be the same as its configuration in Siemens software. As above picture for example, setting is “3”,
that the switch DIP1 and DIP2 on the panel of profibus are set ON, others are OFF.
(2)Profibus support baudrate as follows: 9.6Kbit/s, 19.2Kbit/s, 45.45Kbit/s, 93.75Kbit/s, 187.5Kbit/s,
0.5Mbit/s, 1.5Mbit/s, 3Mbit/s, 6Mbit/, 12Mbit/s,and interface is automatically adaptive.
(3)A cable (purple),connect DP interface of s7-300 and bus bridge of profibus. Two sides have active
terminal resistors; Switch on the s7-300 PLC is off, on the busbridge is on.
( 4) Setting baudrate of modbus by switching DIP1-3 of modbus ID port, support 8 kinds of
baudrate .Setting as follows:
1 2 3 Baud
OFF OFF OFF 1200
ON OFF OFF 2400
OFF ON OFF 4800
ON ON OFF 9600
OFF ON ON 57600
(5)Setting station number of modbus by switching DIP4-8 of modbus ID port ,support 1 to 30 kinds of
station number(DIP4 is lowest bit,DIP8 is highest bit, if DIP4 is on and DIP5~8 is off, it means station
number is 00001,that is No. 1 station).
◎Cable Diagram
RS232 communication cable
HMI terminal
9pin D-SUB female\male
Controller Modbus port terminal
9 pin D-SUB (male)
com2
3 TX
2 RX
5 GND
8 TX
7 RX
5 GND
com0/com1
3 TXD
2 RXD
5 GND
RS485-4 communication cable
HMI terminal
9pin D-SUB female\male
Controller Modbus port terminal
9 pin D
-SUB (male)
6 TD-
8 RD-
5 GND
1 TD+
9 RD+
1 RD-
4
TD-
5 GND
6 RD+
9 RD+
com0/com1
- 138 -