Installation
3-1
TIWAY 1 Ti505 NIM User Manual
Chapter 3
Installation
3.1 GENERAL REQUIREMENTS
The
following requirements must be met in order to install and use a TI505 NIM:
1.
The appropriate NIM should be selected.
PPX:505–7339 (Redundant Local Line)
PPX:505–7340 (Redundant RS-232-C)
2. The TI505 NIM must be used with a model SIMATIC TI525 or SIMATIC
TI535
P/C. For full NIM capabilities, the P/C software release level should be
greater
than (or equal to) the following releases.
TI525
Release 2.2
TI535
Release 1.0
If
you cannot determine whether your P/C release is compatible with the TI505
NIM,
contact
your Siemens Industrial Automation, Inc. distributor or sales of
-
fice
for
assistance. If you need assistance in contacting your distributor or sales
office
in the United States, call 1–800–964–41
14.
3. The
communication configurations of all devices attached to
the network must
match;
i.e., they should each have the same data rate, encoding, etc.
4. Calculate
the I/O base power budget to make sure that there is enough power to
operate
all the modules installed in the base. T
able 1 provides the power
require
-
ments
for all currently available TI505 I/O modules.
NOTE
If
you are not going to install your NIM immediately
, store it in
an
antistatic bag until you are ready for installation.