1-6 DESCRIPTION
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL | CHAPTER 1
RPM Printer Interface The RPM Printer Interface provides a parallel port to the
FireFinder-XLS system. The RPM is compatible with the
PAL-1 printer.
CAB Enclosures The FireFinder-XLS system can be housed in one of
three enclosures: CAB1, CAB2, or CAB3. The CAB1 is a
single-row enclosure that consists of a backbox, front
door and inner door that is shipped assembled. The
CAB2 and CAB3 are two-row and three-row enclosures
respectively with the backbox and doors (inner and
outer) shipped separately.
HTSW-1 Tamper Switch The HTSW-1 Tamper Switch is a three-position switch that monitors
the opening of the FireFinder-XLS enclosure and reports a security
condition. Closing the door automatically returns the switch to its
normal operating position. The switch can be pulled out to indicate a
closed position for maintenance purposes.
Batteries The BP-61 is a 24V 15 AH battery. The BP-61 is recommended
for the NFPA 72 Local and 72 Proprietary and the UL 1076
Systems. Actual battery size depends on System configuration.
See the Battery Calculation section of the PSC-12 Installation
Instructions, P/N 315-033060, for further information.
The BTX-1 batteries are a pair of 12V, 33 AH batteries that are
housed in the bottom of the CAB enclosure. The BTX-2 batteries
are a pair of 12V, 75 AH batteries. The BTX-3 batteries are a pair
of 12V, 100 AH batteries. Actual battery size depends on System configuration.
See the Battery Calculation section of the PSC-12 Installation Instructions,
P/N 315-033060, for further information.
OPTIONAL MODULES The modules listed below are available as options to the FireFinder-XLS system.
CRC-6 Relay Module Each CRC-6 module provides six fully programmable relays. Each relay
contains one set of SPDT contacts rated at 4A, 30 VDC/120 VAC resistive and
3.5A, 120 VAC (0.6 PF) inductive. All relay coils are supervised to ensure
proper operation.
Individual relays can be automatically activated or deactivated through control
by event and time based logic contained in FireFinder-XLS. Each relay may
also be either manually controlled or may be disarmed through the PMI.
HNET
RELAY1
RELAY5
RELAY4
RELAY2
RELAY3
RELAY6
CARD FAIL
24V FAIL
HNET FAIL
RESET
POWER
CRC-6
+
-
1
+
-
2
+
-
3
BACKBOX
OUTER DOOR
INNER DOOR
MOUNTING PLATE