CAUTION
ALL WIRING MUST BE DONE AS DESCRIBED BELOW
TO OBTAIN SAFE AND PROPER SYSTEM OPERATION.
1. Earth ground the FireFinder-XLS enclosure properly; see the latest edition of the
National Electrical Code or CAN/ULC-S524-01 Canadian Electrical Code for
approved methods. Conduit ground is NOT adequate.
2. To wire the System in compliance with NEC Article 760, refer to the Power
Limited Wiring Instructions for the CAB1 Enclosure, P/N 315-033007, or the
CAB2-BB/CAB3-BB, P/N 315-033009, as applicable.
3. INSULATE ALL CABLE DRAIN WIRES from any conduit or earth grounded
electrical box, including those in the FireFinder-XLS enclosure.
4. Connect shield cable drain wire ONLY inside the FireFinder-XLS enclosure.
5. No wiring used for any of the following can run outside the building:
• a DLC loop
• an RS-485 network
• a NAC circuit used for audibles, audio, and telephone risers
• an HZM initiating device zone
For additional wiring
information, refer to this
manual or call Siemens
Building Technologies,
Inc. Technical Support
Department at
1-800-248-7976.