Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
A-13
Number Effect/cause Remedy
140015 Incorrect baud rate
or:
incorrect bus parameter (e.g.I)
or:
OP address > I or: incorrect interrupt vector
(interrupt does not arrive at the driver)
Correct the incorrect parameters.
140016 Configured interrupt is not supported by the
hardware.
Change the interrupt number.
140017 Configured interrupt in use by another driver. Change the interrupt number.
140018 The consistency check was deactivated by
SIMOTION Scout. Only one appropriate note
appears.
Activate the consistency check with SIMOTION Scout
again and reload the configuration in the project.
140019 SIMOTION Scout loads a new project to the PLC.
Connection to the PLC is interrupted.
Wait until the end of the reconfiguration.
140020 The version in the PLC and that in the configuration
(FWX file) do not match.
Connection to the PLC is interrupted.
The following remedies are available:
Load the current version in the PLC using SIMOTION
Scout.
Regenerate the project using WinCC flexible ES, close
WinCC flexible Runtime and restart with a new
configuration.
150000 No additional data is read or written. Possible
causes:
• The cable is defective.
• The PLC does not respond, is defective, etc.
• The connection is established via the wrong
interface.
• The system is overloaded.
Check that the cable is plugged in, the PLC is operational
and the correct interface is used.
Reboot the system if the system alarm is displayed
continuously.
150001 Connection is
!
e-established because the cause
of the interruption has been eliminated.
-
160000 No additional data is read or written. Possible
causes:
• The cable is defective.
• The PLC does not respond, is defective, etc.
• Connection has been established via the wrong
interface.
• The system is overloaded.
Check that the cable is plugged in, the PLC is operational
and the correct interface is used.
Reboot the system if the system alarm is displayed
continuously.
160001 Connection is
!
e-established because the cause
of the interruption has been eliminated.
-
160010 There is no connection to the server because the
server identification (CLS-ID) cannot be
established.
Values cannot be read or written.
Check the access rights.
160011 There is no connection to the server because the
server identification (CLS-ID) cannot be
established.
Values cannot be read or written.
For example, check if
• The server name is correct
• The computer name is correct
• The server is registered