Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
A-17
Number Effect/cause Remedy
200103 Coordination can be executed again because the
last error status has been eliminated (return to
normal operation).
-
200104 The coordination may not be executed. -
200105 No additional data is read or written. Possible
causes:
• The cable is defective.
• The PLC does not respond, is defective, etc.
• The system is overloaded.
Check that the cable is plugged in and the PLC is
operational.
Reboot the system if the system alarm is displayed
continuously.
210000 Jobs are not processed because the address
configured in the PLC does not exist/has not been
set up.
Change the address or set up the address in the PLC.
210001 Jobs are not processed because the address
configured in the PLC cannot be written to/read
from.
Change the address or set up the address in the PLC in
an area which can be written to/read from.
210002 Commands are not executed because the address
format of the area pointer does not match the
internal storage format.
Internal error
210003 The job mailbox is processed again because the
last error status has been eliminated (return to
normal operation).
-
210004 It is possible that the job mailbox is not processed. -
210005 A controller job with an illegal number was
triggered.
Check the PLC program.
210006 An error occurred while attempting to execute the
controller job. As a result, the controller job will not
be executed. Note the subsequent/previous system
alarm, if appropriate.
Check the parameters in the controller job. Recompile the
configuration.
220001 The tag is not downloaded because the associated
communication driver / HMI device does not
support downloading the data type bool/bit.
Change the configuration.
220002 The tag is not downloaded because the associated
communication driver / HMI device does not
support the data type byte when writing.
Change the configuration.
220003 The communication driver cannot be loaded. The
driver may not be installed.
Install the driver by reinstalling WinCC flexible Runtime.
220004 Communication is terminated and no update is
executed because the cable is not connected or is
defective, etc.
Check the connection.
220005 Communication is running. -
220006 The connection is established to the specified PLC
at the specified interface.
-