Setting Up and Operating the Computing Unit
3-17
SIMATIC Panel PC 670 Computing Unit Equipment Manual
Edition 12/01
3.7 Using the Computing Unit in a SIMATIC S5 Network
Point-to-point connection,
This section describes the options for connecting your computing unit to a
programming unit or an S5 programmable controller in a point-to-point connection.
A point-to-point connection is possible by connecting the computing unit to another
programming unit or a programmable controller by means of:
S a V.24 connection
S a TTY connection
Configuring notes for interfaces with current loop (TTY, 20 mA)
Different criteria have to be taken into account for reliable operation of a
connection. The maximum data transfer rate (baud rate) depends on the required
distance, the type of cable, the pin assignment of the interface and external
interference.
Rules
To reduce interference by a favorable choice and correct connection of the
cable, you should comply with the following rules:
S The shielded cable used must have a low line resistance
(< 130 W / km) and a low capacitance (< 90 pF/ m). Twisted-pair cables are
less susceptible to inductive interference. A low line resistance result in reduced
voltage excursions and shorter charge reversal times; the line resistance
decreases with increasing conductor cross-section for the same length of cable.
S The shorter the data transmission link, the higher the maximum possible
transfer rate.
S If there is an active transmitter and an active receiver at the same end of the
transmission link, the sequence of access priority to the transmission circuit
must be taken into account in order to achieve the longest possible
transmission link.
S Signal lines and power lines must not be run together. Signal lines must be
installed as far away as possible from sources of strong interference (for
example, 400 V 3-phase power cables).
S The active TTY interface with a 12 V open-circuit voltage has been tested on a
100 m long cable at a transmission rate of 9600 bps in an environment with
normal levels of noise (field strength < 3 V/ m). If a LiYCY 5 x 1x 0.14 shielded
cable is used, reliable transmission is possible over a distance of up to 100 m.
The AS511 driver was used for testing (only one transmitter at a time).
Note
The interference field of the source of interference is reduced by the square of
the distance.