– The FC726 is a modular fire control panel with integrated operating unit which
processes signals from Cerberus PRO FD720 and SynoLOOP devices.
– An integrated card cage with 5 slots allows
– C-NET line cards FCL2001-A1 to be used (for extra lines)
– SynoLOOP line cards, FCL 7201-Z3
– I/O card FCI2008-A1 (with 12 programmable inputs/outputs)
– Mixed use of all line and I/O cards possible.
– In the event of a defect, the extra line cards can be replaced without the control panel
having to be powered down.
– The fire control panel may be used as a stand-alone unit or networked.
– The control panel can be programmed into a system with high levels of flexibility us-
ing a user-friendly configuration tool (software).
– Adaptation of customer texts on the terminal itself or using the configuration tool.
– Up to 2000 events can be called up for each station according to various criteria.
– Automatic summer/winter time changeover.
– Integration to Siemens Danger Management System
Functional elements
Operating unit
The following are located on the operating unit:
– CPU module and electronic components for operating unit
– Ethernet connection
– Plug-ins for RS232, RS485 modules and networking modules (SAFEDLINK)
– Space for 'Kaba' or 'Nordic' key switch
– Space for event printer
Periphery board
The following are located on the peripheral board:
– Connection terminals for C-NET loops, remote transmission (alarm, fault), horn
outputs, programmable control inputs/outputs, monitored alarm and fault output,
degrade supply, power supply
– 2 plug-ins for loop extension (C-NET)
Card cage (5 slots)
There is a card cage on the rear housing panel for use of max. 5 line cards
- C-NET line cards,
- SynoLOOP line cards and/or I/O-cards.
Power supply unit 150 W, emergency power supply
The power supply supplies the hardware and charges the batteries
– The batteries supply the emergency power in case of power failure
Housing
A pivoting mounting panel can be installed on the housing backplane to allow installa-
tion of:
– 1 fire brigade periphery module
– 2 sounder modules (can also be mounted onto the U-rail TS35)
Configuration
The FXS7212 Cerberus engineering tool permits the system to be adapted to specific
customers' requirements.