POWERS™ Controls No. 4 Pneumatic Damper Actuator Technical Instructions
Document Number 155-032P25
October 10, 2005
Siemens Building Technologies, Inc. Page 9
Extended Shaft
Mounting - Fixed
Actuator
1. Order one of the following damper actuators, the clevis, and linkage kit (Figure 8):
Actuator with mounting bracket: 331-2911, 331-2966, 331-2927, or 331-2974
Clevis: 331-801
Linkage Kit: 331-958
2. Determine the application, and select appropriate "X" and "Y" dimensions from
Table 7. Select a rigid section of the duc
t, if possible, and then draw these lines on
the duct.
NOTE: If the "X" dimension is 8-1/2 inches (216 mm), place the rear of the
actuator against the damper shaft and draw a line along the front of the
bracket for the "X" dimension.
Measure the “Y” dimension.
3. If the actuator assembly mounts to the right of the damper shaft (Figure 8):
•
Draw the "Y" dimension line above the damper shaft if the damper blade is to
rotate CCW as actuator pressure increases.
• Draw the "Y" line below the damper shaft if the damper blade is to rotate CW as
actuator pressure increases.
If the actuator assembly mounts to the left of the damper shaft:
• Draw the "Y" dimension line above the shaft if the damper blade is to rotate CW
as actuator pressure increases.
• Draw the "Y" line below the damper shaft if the damper blade is to rotate CCW
as actuator pressure increases.
CAUTION:
It is important to use the "X" and "Y" dimensions in Table 7 to position the
actuator. They were selected to ensure that the crank is approximately
perpendicular to the actuator shaft at half its stroke. This will prevent the
linkage from scissoring or locking up (see Figure 7).
AP0254R1
CRANK
SHAFT
PIVOT
POST
MOUNTING
PLATE
PIVOT POST AND CRANK SHAFT
MUST REMAIN PERPENDICULAR
TO MOUNTING PLATE
Figure 7. Perpendicular Mounting.
Kommentare zu diesen Handbüchern