Control via the Operator Panel 04/04
SINAMICS G130 - Operator Panel AOP30
5-16 Operating Manual
At access level 3 (experts), you can change the structure of the function by
interconnecting BICO parameters. For this reason, this access level is password
protected (password: "47").
The parameter list displays more options than there are function keys. You can use
the "<<" key to change the function of the keys. To return from the second menu,
press F5 (">>"). Once a function is complete, the system automatically returns to
the main menu.
F1 "Help", F2 "DS Select", and F3 "EEPROM" are available in the extended menu.
In the DS Selection menu (data set selection), you can choose which of the data
sets chosen is currently DISPLAYED.
Data set parameters are indicated by a “c”, “d”, “m”, or “e” between the parameter
number and parameter designator. The second line from the top (aligned right)
shows which data sets are currently displayed.
5.5 Menu: Fault/Alarm Memory
Faults
Shows which faults are currently present (max.: 8).
To select one of the faults, choose F2. To call up a description of causes and
possible remedies, choose F1 "Help". The fault value, which allows more effective
diagnosis, is specified in the second line in Help.
To acknowledge the fault, choose F5 "Ack.". Once you have successfully
acknowledged the fault, the system returns to the calling screen. If the fault cannot
be acknowledged, the fault screen continues to be displayed.
To display the last eight faults, choose F3 "Old". The system then displays seven
acknowledged faults (1st – 7th fault).
Alarms
Displays the current content of the alarm buffer. Alarms present at the time the
screen was opened are displayed accordingly.
To refresh the display, choose F5: "Refresh". To delete the alarm buffer and rebuild
it so that it only contains the currently active alarms, choose F3 "Delete".