Control via the Operator Panel 04/04
SINAMICS G130 - Operator Panel AOP30
5-22 Operating Manual
5.7 Operation via the Operator Panel (LOCAL Mode)
You activate the control keys by switching to LOCAL mode. If the green LED in the
LOCAL/REMOTE key does not light up, the key is not active.
5.7.1 LOCAL/REMOTE Key
Activate LOCAL mode: press the LOCAL key
LOCAL mode: LED lights up
REMOTE mode: LED does not light up: the ON, OFF, JOG, direction reversal,
faster, and slower keys are not active.
Settings: Menu: Commissioning / Service – AOP Settings – Control Settings
Save LOCAL mode (factory setting: yes)
• Yes: "LOCAL" or "REMOTE" operating mode is saved when the supply voltage
is switched off, and restored when the supply voltage is switched back on.
• No: "LOCAL" or "REMOTE" operating mode is not saved. "REMOTE" is active
when the supply voltage is switched back on.
LOCAL/REMOTE also during operation (factory setting: no)
• Yes: You can switch between LOCAL and REMOTE when the drive is switched
on (motor is running).
• No: Before the system switches to LOCAL, a check is carried out to determine
whether the drive is in the operational status. If so, the system does not switch
to LOCAL and outputs the message "Local not possible". Before the system
switches to REMOTE, the drive is switched off and the setpoint is set to 0.