Installation Instructions
Rating Plug
CAUTION
!
3. Check label on the rating plug.
Check the rating plug label to verify that it is the correct plug
for the trip unit. If it is not a correct plug, the pins will not mate
with the plug receptacle.
4. To insert rating plug, align plug with plug receptacle and press into
place.
To
insert
a rating plug in the trip unit, align the plug with the
plug receptacle and press the plug into place. The clips on the
plug secure the plug, eliminating the need for screws or
latches.
To
remove
a rating plug, squeeze the clips and pull the plug
from the plug receptacle. Because the plug is held in place by
compression, some force is required to remove the plug.
Do
not close
the breaker with the rating plug removed from the
trip unit.
5. To replace the cover, bow it slightly in the middle and snap into
place.
After the rating plug has been inserted and the necessary set-
ting adjustments have been made, replace the cover by sliding
the protective shield into the top lip of the trip unit, bow it
slightly in middle, and press it down with your thumb on
bottom to snap shield into place. Replace the two special
retaining screws.
NOTE: For more complete information on the electronic
trip units, see Siemens Electronic Trip Units for SB
Encased Systems Breakers Information and Instruction
Guide Bulletin IPIM-2203 and the Sentron Systems
Breaker Energy Communicating Trip Unit Information and
Instruction Guide Bulletin IPIM-2208.
6. The cover may be sealed with a lead seal for tamper evident
protection.
After the cover has been replaced, a wire may be inserted
through the holes in the screws and secured with a meter
seal. This will help prevent tampering.
Do not attempt to force an incorrect
rating plug into a trip unit. Mechanical
damage may occur. The receptacle in the
trip unit has been keyed to prevent the
insertion of an incorrect rating plug.