External Accessories
Siemens ACCESS Communications System
SB Breaker Communication
All SB Circuit Breaker trip units feature two levels of communi-
cation: Zone Selective Interlocking and ACCESS System open-
protocol communications. The SB-EC Trip Unit is fully equipped
for direct integration into ACCESS or compatible communica-
tion systems. It does not require a MTA (Muliplexer/Translator
for ACCESS communications and Zone Interlocking) or expan-
sion plug (EP).
If zone selective interlocking alone is specified for a SB-EC or
TL Trip Unit, a MTZ (Muliplexer/Translator for Zone Interlock-
ing) and an EP are required.
If zone selective interlocking and full ACCESS communications
are specified for a TL Trip Unit, a MTA and an EP are required.
The MT (as in MTA and MTZ) is a minicomputer that collect
data from and transmit data to difference components
integrated into the ACCESS communications system. The MT
can support up to eight field devices. Multiple MTs can be
connected, although an expansion plug may be required for
each trip unit.
Siemens WinPM supervisory software (version 4.0 or later)
delivers a powerful energy management system providing
sophisticated monitoring capability to a host computer and
other components in the electrical distribution system at
affordable cost. It also provides process control, including peak
demand, trend analysis, waveform analysis, and harmonic
calculations and displays. These functions help pinpoint energy
consumption, power quality issues, and the energy cost of any
process. Outages and potential outages can be quickly
diagnosed and plans can be generated for expansion and
preventative plant maintenance.
NOTE: Refer to Bulletin IPIM-2211 for additional informa-
tion on the MTA and Siemens WinPM software.
Communications is accomplished via EIA-485 twisted pair
wire or modem. It provides communications to a remote site
and allows access to multiple plants. WinPM uses a Microsoft
Windows dynamic data exchange (DDE) server that allows
data exchange to other Windows-based software such as
spreadsheets and word processors.
Protocol Converters are available from the Siemens ACCESS
group for connecting a variety of open and proprietary automa-
tion protocols, including Profibus DP, LonWorks, Siemens S7
PLC, and many other third-party PLCs and associated net-
works. The SB-EC Trip Unit’s EIA-2342 communications port
provides additional PC communications for available trip unit
data displays and trip unit configuration via Siemens SBWIN
software. Remote open/close operation is also possible if a
remote open/close relay is installed.
Expansion Plug
Factory wired when ACESS communications or ZSI is ordered for
the SB breaker from the factory.
The EP is an electronic interface and isolation module required
to integrate a breaker into an ACCESS system. When required,
one expansion plug is used for each circuit breaker in the
system and is used to interface trip units to a MTZ or MTA.
The expansion plug is always necessary for zone interlocking
or full ACCESS communications for the TL Trip Unit. It is not
required for ACCESS communications with the SB-EC Trip
Unit. However, an expansion plug is required for zone inter-
locking with the SB-EC Trip Unit.
Expansion Plug Dimension Drawing
SB Systems Breakers
The following sections describe both types of SB trip units,
the standard Type ‘TL unit with rotary switches, and the SB
Energy-Comm (SB-EC) Trip Unit with keypad and display. Since
the SB-EC Trip Unit has integral communications capability, the
MTA device is not
required to connect within an ACCESS sys-
tem, however for SB-EC Trip Units in a ZSI system, an MTZ or
MTA is required.
The type EPSB expansion plug is factory wired to the SB
breaker trip unit’s rear connector and also located near and
wired to the SB breaker’s secondary terminal block for fixed
mount breakers or sliding disconnects for drawout breakers.
These connections are factory wired when the SB breaker is
ordered with the standard switch based type ‘TL trip unit for
ACCESS communications or for any trip unit with ZSI capability.
Installed ICCB SB breakers without communication capability
may be field upgraded for communication capability by
Siemens Field Service personnel only
.
Breaker Type Frame Size Mounting Type Cat. No.
SB ICCB 1200A, 2000A Fixed EPSBFMK
Drawout EPSBDMK
SB ICCB 3200A, 5000A Fixed EPSB4FMK
Drawout EPSB4DMK
Sensitrip
MCCB
ALL ALL
EP
EPSB