Seitenansicht 28
How to configure an Anybus PROFIBUS Slave module with a Siemens Step7 PLC
SCM-7032-026
Rev 2.1
Figure 34 Troubleshooting the PROFIBUS network.
Carrying out the tests
Configuration A: Set switch of test connector 1 to position 3 (connects pin 3 to the screen). Connect
ohmmeter to test connector 2 between pin 3 and the screen.
Configuration B: Set switch of test connector 1 to position 8 (connects pin 8 to the screen). Connect
ohmmeter to test connector 2 between pin 8 and the screen.
Configuration C: Set switch of test connector 1 to position 3 (connects pin 3 to the screen). Connect
ohmmeter to test connector 2 between pin 8 and the screen.
Configuration D: Switch position of test connector 1 is not important. Connect ohmmeter to test
connector 2 between pin 3 and pin 8.
Warning: The measured value can be falsified if the ohmmeter connections are touched.
www.anybus.com HMS Industrial Networks AB