Simatic/TI 505 Ethernet Driver Help
0 = Status is good.
1 = Base is not present or has a problem.
Bit 1, Base 15
Bit 2, Base 14
Bit 3, Base 13
Bit 4, Base 12
Bit 5, Base 11
Bit 6, Base 10
Bit 7, Base 9
Bit 8, Base 8
Bit 9, Base 7
Bit 10, Base 6
Bit 11, Base 5
Bit 12, Base 4
Bit 13, Base 3
Bit 14, Base 2
Bit 15, Base 1
Bit 16, Base 0
STW00003-00009 Profibus DP Slave Status
Each bit is 0 if a slave is present, or 1 if the slave is
missing or failed.
STW03 Bit 1-16 slave addresses 16-1
STW04 Bit 1-16 slave addresses 32-17
STW05 Bit 1-16 slave addresses 48-33
STW06 Bit 1-16 slave addresses 64-49
STW07 Bit 1-16 slave addresses 80-65
STW08 Bit 1-16 slave addresses 96-81
STW09 Bit 1-16 slave addresses 112-97
x x x x
STW00010 Contains the value of the previous dynamic scan
time.
x x x x
STW00011 Indicates the status of the modules in the Local
Base (Base 0). Each bit indicates a module in a
slot.
0 = Good
1 = Module not present or failed
Bit 1 - 16 = Module 16 - 1
x x x x
STW00012-00026 Status bits for modules in bases 1 - 15, STW012 =
Base 1…
Bit range is the same as for STW011.
x x x x
STW00027-00138 This range of Status Words apply to the Profibus
DP slave channels if present. STW027 is slave
1…STW138 is slave 112.
Bit range is the same as for STW011.
x x x x
STW00139 This Status Word provides a count of the discrete
points (X/Y or C) that are currently forced.
x x x x
STW00140 This Status Word provides a count of the word
points (WX/WY) that are currently forced.
x x x x
STW00141-00144 Date, Time, and Day of Week N/A N/A N/A N/A
STW141 Bit 1-4, Year tens digit
Bit 5-8, Year units digit
Bit 9-12, Month tens digit
Bits 13-16, Month units
x x x x
STW142 Bit 1-4, Day - Tens digit
Bit 5-8, Day - Units digit
Bit 9-12, Hour - Tens digit
Bit 13-16, Hour - Units digit
x x x x
STW143 Bit 1-4, Minute - Tens digit
Bit 5-8, Minute - Units digit
x x x x
www. kepware.com
17