Simatic/TI 505 Ethernet Driver Help
Data type <type> is not valid for device address <address>.
Error Type:
Warning
Possible Cause:
A tag address that has been specified dynamically has been assigned an invalid data type.
Solution:
Modify the requested data type in the client application.
Device address <address> contains a syntax error.
Error Type:
Warning
Possible Cause:
A tag address that has been specified dynamically contains one or more invalid characters.
Solution:
Re-enter the address in the client application.
Device address <address> is read only.
Error Type:
Warning
Possible Cause:
A tag address that has been specified dynamically has a requested access mode that is not compatible with what
the device supports for that address.
Solution:
Change the access mode in the client application.
Device <device name> cannot execute a read request (<address>, <size>).
Error Type:
Serious
Possible Cause:
The device is unable to return the amount of read data requested in one request.
Solution:
Adjust the requested block size on the device so that the driver makes smaller requests.
Device <device name> cannot execute a write request (<address>, <size>).
Error Type:
Serious
Possible Cause:
The device is unable to receive the amount of write data sent in one request.
Solution:
Adjust the array size on the address so that a smaller amount of data is sent to the device in one transaction.
Device <device name> detected a NITP protocol error (tag <address>, size
<size>).
Error Type:
Serious
Possible Cause:
This error may occur when sending Packed Task Code messages. The device is experiencing network errors.