Figure 15
Then, click on Address details. This popup window is important as it contains communication information to
setup the G306 in Crimson 2 (Figure 16). They are as follows:
1. PLC Connection Resource
2. PLC TSAP information. The first part of the number, before the decimal point represents the
Server Connection Resource, the second part is the rack slot number where the CP343 is installed.
In this example, the Connection Resource is 10 and the slot 04.
3. Partner Rack/Slot, they should stay at zero.
4. Partner Connection Resource, this number can be different from the PLC Connection Resource.
Figure 16
Click OK to close all popup windows and go back to NetPro. The table now shows the connection just created
on the first line.
Save and compile in NetPro and close this window to go back to the project manager.
The PLC is now setup. Download the configuration and make sure the PLC takes the entire configuration, especially
the connection settings. We recommend using the command “PLC > Compile and Download Objects…”
1