SETUP 3 – COMMUNICATION VIA CP343 OPTIONAL ETHERNET CARD NOT
SUPPORTING TSAP CONNECTIONS (TRANSPARENT MODE)
The following setup is required if you are using a CP343-1 Lean module.
Setting up the PLC for CP343 communication
Start SIMATIC Manager and follow the wizard to create a new project. This example is using a CPU315-2DP,
and a CP343-1 Lean. Once created, the project browser should look similar to figure 21.
Figure 21
Select the SIMATIC 300 PLC in the tree and double click the Hardware symbol to access HW Config.
Once in HW Config, browse the object library on the right hand pane to find the optional Ethernet card CP343-1
Lean. Drag and drop the card to an available slot as shown in figure 22.
Figure 22
Seitenansicht 13