Installing the Module
2-10
SIMATIC 505 PROFIBUS-FMS CP User Manual
2.7 Configuring the I/O Address in the Programmable Logic Controller
After
installing the FMS CP module in the base, you need to register the I/O
starting address of the FMS CP module in your programmable logic
controller memory
. The module does not automatically register its I/O
address in the programmable logic controller
.
NOTE:
Even though the module may appear to be operating correctly
, if it is
not configured in the I/O map, it cannot support communication jobs or
Peerlink transfers, and server function requests run slowly
.
T
o configure the I/O map and verify controller
-to-module communications,
connect a programming device with base configuration software (for
example, TISOFT) to the programmable logic controller
, and follow the steps
below
. For detailed instructions about using TISOFT to configure the I/O
slot in the base, see the
SIMA
TIC 505 TISOFT2 Release 6.0 User Manual
,
PPX:TS505–8101–6 or higher
.
NOTE:
Ensure that the FMS CP module successfully completes power
-up
initialization before you attempt to configure the I/O slot in the base.
1.
In TISOFT
, access the Configure I/O function menu.
2.
Select the appropriate channel and base number
.
3.
Execute the Read Base function.
The module appears as a 4 WX 4 WY Special Function module, as
shown in Figure 2-8. It uses 8 I/O address locations.
4.
Assign the starting I/O address and write the completed I/O
configuration to the programmable logic controller memory
, using the
W
rite PLC function.