Remote Station Address Enter
the PROFIBUS network address used
by the remote device.
Remote LSAP Enter
a numeric value for the Link Service Access Point
for the FMS connection on the remote device. Choose a value between 2
and 62. Y
ou cannot use the same LSAP more than once at the same
remote station (refer to T
able A-10 for LSAP assignments).
Maximum PDU Size TX High Specify
the maximum number of bytes for
Protocol Data Units that can be sent on high priority transmissions.
Maximum PDU Size TX Low Specify
the maximum number of bytes for
Protocol Data Units that can be sent on low priority transmissions.
Maximum PDU Size RX High Specify
the maximum number of bytes for
Protocol Data Units that can be received on high priority receptions.
Maximum PDU Size RX Low Specify
the maximum number of bytes for
Protocol Data Units that can be received on low priority receptions.
Data Transfer Type Select
the type of data transfer and relationship
between the remote device and the FMS CP module. (See T
able
A-8 for
details on transfer types and jobs allowed.)
Maximum Confirmed Services To Specify
the maximum number of
confirmed concurrent services that can be sent to the remote station.
Maximum Confirmed Services From Specify
the maximum number of
confirmed concurrent services that can be received from the remote
station.
Maximum Unconfirmed Services To Specify
the maximum number of
unconfirmed concurrent services that can be sent to the remote station.
Maximum Unconfirmed Services From Specify
the maximum number of
unconfirmed concurrent services that can be received from the remote
station.
Control Interval Specify
the maximum time allowed between
commands on the bus in 10 ms intervals.
Multiplier
Specify how many times this connection is entered into the
poll-list. A higher value gives this connection a higher priority relative
to other connections (used only for some master
-slave connections).
Password
Enter a numeric value as the password. This password, if
used, must match the password specified for the variable at the remote
partner
. 0 = Access is possible for
all
FMS clients that specify a
password of 0. T
o specify access restricted by password, the valid range
is 1 to 255. Refer to Section 4.3 for more information.