Using the COM5434 Configurator
5-16
SIMATIC 505 PROFIBUS-FMS CP User Manual
5.5 Defining Peerlink II Services
The
FMS CP module supports a maximum of 32 Peerlink II services, as
shown in Figure 5-9. The FMS CP module transmits and receives data (in
the form of peer blocks) to and from other SIMA
TIC 505 FMS CP modules
on your network on a scan-by-scan basis. When you click on Peerlink II
Services on the configuration tree, the COM5434 Configurator displays the
number of T
ransmit and Receive blocks available.
✂
File Edit Transfer Options Diagnostics Help
Untitled
– COM5434
Configured
cyclic data blocks sent/received to/from other 505-CP5434-FMS modules
FMS Connections
FDL Connections
Communication Jobs
FMS Jobs
Send-Receive Jobs
FMS Data T
ypes
FMS
FDL
FMS
P–P
S–R
DTs
FMS V
ariables
<no description>
Module Local Configuration
Peerlink II Services
10
Peer Receive Blocks Available:
31
Peer Priority Factor:
8
Maximum Peer Blocks:
Peer Transmit Blocks Available:
32
1
Peer T
ransmit Interval:
Click here.
Figure 5-9 Peerlink
II Services A
vailable
T
o configure Peerlink II Services, define the desired transmission interval
and priority factor
, and then configure the individual peer function blocks.
Peer Transmit Interval Enter
a numeric value, from 0 to 65,535 (scan
cycles), to specify how often the T
ransmit peer block transmission is
attempted.
Peer Priority Factor Enter
a numeric value, from 0 to 8, to specify the
priority for writing received peer data blocks to the PLC versus other
communications activities (e.g., FMS jobs). A factor of 8 specifies the
highest priority for received peer data, but still allows other activities if
no peer receives are pending. A factor of 0 is the lowest priority
, but
still allows peer receives if no other activities are pending.