7.22 Simulation
7.22.1 Overview of simulation
Description
With the "Simulation" diagnostic function, you can receive and process simulated
measurement data onsite or in the control room without having process pressure or a
temperature value. This allows you to run individual process sequences in the "cold" state and
thus simulate process states. In addition, if you inject simulation values you can test the line
routing from the control room to the individual transmitter.
The value to be simulated can be provided as a fixed value or in the form of a ramp function.
Simulation of pressure and temperature values is handled in the same way in terms of
parameter settings and function, so the following will only deal with the general simulation
procedures "Fixed value" and "Ramp function".
For reasons of safety, all simulation data are held only in the non-volatile user memory. This
means that when the device is restarted any simulation which may be active will be shut down.
You can simulate the pressure and both temperature values. It should be noted here that
changing the temperatures by simulation will have no effect on the measured pressure value.
$
'
'
$
+$57
+$57
&RPPXQLFDWRU
w&
0HDVXUHPHQW
3URFHVVYDOXH
P$
6HQVRU
7HOHFWU
9DOXHV
7VHQVRU
)L[HGYDOXH
9DOXHV3
5DPS
9DOXHV
7HOHFWU
,
&RQVWDQW
6LPXODWH
6HQVRU
S
6HQVRU
7
Figure 7-18 Block diagram of simulation
Operating functions through HART
7.22 Simulation
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 133