3. Open the differential pressure valve ( or ).
4. Check
and if required correct the zero point when the start of scale value is 0 mbar (4 mA).
5. Close the stabilizing valve .
6. Open the other differential pressure valve ( or ).
9.4.3 Commissioning for liquids
Usual arrangement Special arrangement

 
Pressure transmitter Drain valves
Equalizer valve Gas collector vessels (optional)
, Differential pressure valves Differential pressure transducer
Differential pressure lines Vent valves
Shut-off valves
Transmitter below the differential pressure
transducer
Transmitter above the
differential pressure transducer
Condition
All valves are closed.
Commissioning
9.4 Differential pressure and flow rate
SITRANS P, DS III series with HART
Operating Instructions, 09/2012, A5E00047092-08 155