Procedure
To commission the transmitter for gases, proceed as follows:
1.
Open the shut-off valve for the test connection ④.
2. Via the test connection of the shut-off fitting ②, apply the pressure corresponding to the
start of scale value to the pressure transmitter ①.
3. Check the start of scale value.
4. If the start of scale value differs from the value desired, correct it.
5. Close the shut-off valve for the test connection ④.
6. Open the shut-off valve ⑥ at the pressure tapping point.
7. Open the shut-off valve for the process ③.
9.3.2 Commissioning with steam or liquid
① Pressure transmitter
② Shut-off fitting
③ Shut-off valve to process
④ Shut-off valve for test connection or for bleed screw
⑤ Pressure line
⑥ Shut-off valve
⑦ Blow-out valve
⑧ Compensation vessel (steam only)
Figure 9-1 Measuring steam
Commissioning
9.3 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge
pressure series
SITRANS P, DS III series with HART