3. Wait until the steam in the differential pressure lines and in the equalizing vessels
has condensed.
4.
Open the differential pressure valve and the vent valve on the positive side of the
transmitter slightly, until condensate escapes without bubbles.
5. Close the vent valve.
6. Open the vent valve on the negative side of the transmitter slightly, until condensate
escapes without bubbles.
7. Close the differential pressure valve .
8. Open the differential pressure valve slightly, until condensate escapes without bubbles,
then close it.
9. Close the vent valve on the negative side .
10.Open the differential pressure valve by rotating it in half a turn.
11.Check and if required correct the zero point in case of start of scale value 0 bar (4 mA).
12.Close the stabilizing valve .
13.Fully open the differential pressure valves and .
14.You can briefly open the drain valves to clean the line. Close before steam starts to leak.
Commissioning
9.4 Differential pressure and flow rate
SITRANS P, DS III series with HART
158 Operating Instructions, 09/2012, A5E00047092-08