
Installation UMSITRPDS3-1
November 2010
4-4
4.3.3 Impulse Piping for Absolute and Differential Models
Impulse piping is the piping to be connected to the transmitter’s process connection(s). For suggested
flow and level measurement piping arrangements, refer to:
• Differential Model - Figures 4-1 and 4-2
• Absolute Model - Figures 4-3 and 4-4
• Flange Model - Figure 4-5
Note the following when planning and installing piping.
• Install impulse piping in accordance with ANSI Code B31.1.0.
• Make impulse piping length as short as possible to reduce frictional loss and temperature-induced
pressure variations.
IMPORTANT
When using impulse lines on a high temperature process, locate the transmitter far
enough away from the heat source to keep it within temperature specifications [28°C
(50ºF) per foot cooling to a normal ambient is assumed for non-insulated impulse lines].
• For lines between the process and transmitter, use impulse piping of 3/8" OD or larger to avoid
friction effects (causes lagging) and blockage.
• Use the least number of fittings and valves possible to minimize leakage problems. Teflon
®
tape is the
recommended thread sealant for process connections at the transmitter.
• Valves used in pressure service should be either globe or gate type. Valves used in gas service should
be of a type that does not permit condensate to build up behind the valve.
• Install sediment chambers with drain valves to collect solids suspended in process liquids or moisture
carried with non-condensing gases.
• Install air chambers with vent valves at high point in piping to vent gas entrained in process liquid.
• Remote diaphragm seals can be used to keep corrosive liquid or gas from the transmitter pressure
inlets and isolation diaphragm.
• Alternatively, use sealing fluid to isolate the process from the transmitter. Sealing fluid must be of
greater density than process fluid and non-miscible.
• For transmitters located above the process, slope piping from the transmitter at least 1 inch/foot (83
mm/M) down toward process. For transmitters below the process, slope piping at least 1 inch/foot (83
mm/M) up to process.
• Protect pressure lines (by shielding if necessary) from objects or equipment that may bend or kink the
line causing fluid flow restriction.
• Protect the pressure lines from extreme temperature ranges. Lines should be protected from freezing
by installing a heat trace.
• A three-valve manifold should be used with a differential transmitter model. A two-valve manifold
can be used with an absolute model to permit servicing and zero checks.
Kommentare zu diesen Handbüchern