
Commissioning
9.3 Commissioning part-turn actuators
SIPART PS2 with and without HART communications
122 Operating Instructions, 09/2007, A5E00074631-07
2. Change the actuator type from linear to the part-turn actuator. Change the parameter
setting using the
decrement button. The following is shown on the digital display:
3. Call the second parameter "YAGL". Press the
operating mode button for a short while
for this purpose. This parameter has already been set to 90° automatically. The following
is thus shown on the digital display:
4. Call the fourth parameter "INITA". Press the
operating mode button for a short while
for this purpose. The following is shown on the digital display:
5. Start the initialization process. To do this, press the increment button
for at least 5
seconds until the digital display shows the following:
Note
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN1" to "RUN5" are shown in the
lower line on the digital display. The initialization process depends on the actuator used,
and takes up to 15 minutes.
6. The following display indicates that the automatic initialization is complete. The total
angle of rotation of the actuator is shown on the upper line on the digital display:
Kommentare zu diesen Handbüchern