Alarm, error, and system messages
11.2 Diagnosis
SIPART PS2 with and without HART communications
184 Operating Instructions, 09/2007, A5E00074631-07
rEF (the reference average is calculated)
The function was started, and the reference interval is in progress at the moment.
COMP (the comparison average is calculated)
The function was started, and the comparison interval is in progress at the moment.
20 P0 - potentiometer value of the lower end stop
21 P100 - potentiometer value of the upper end stop
Both these values indicate the measured values of the position displacement sensor
(potentiometer) on the lower or upper hard end stop, as they were determined during
automatic initialization. The values of manually approached end positions are applicable for
manual initialization.
22 IMPUP - impulse length up
This parameter can be set for special applications.
23 IMPDN - impulse length down
The smallest impulse lengths that can be used to move the actuator are determined during
the initialization process. They are separately determined for the "Up" and "Down" directions
and displayed here.
This parameter can be set for special applications.
24 DBUP - dead zone up
25 DBDN - dead zone down
The dead zones of the closed-loop controller in the "Up" and "Down" directions are displayed
here. The values correspond to either the manually set value of the "DEBA" parameter or the
automatically adapted value by the device if DEBA" was set to "Auto".
26 SSUP - slow step zone up
This parameter can be set for special applications.
27 SSDN - slow step zone down
The slow step zone is the zone of the closed-loop controller in which control signals are
issued in a pulsed manner. The impulse length is thus proportional to the control deviation. If
the control deviation is beyond the slow step zone, the valves are controlled using
permanent contact.
This parameter can be set for special applications.