Operating
7.2 Operating modes
SIPART PS2 with and without HART communications
96 Operating Instructions, 09/2007, A5E00074631-07
The following figure shows the operation of the configuration and initialization modes.
VLPXOWDQHRXV VLPXOWDQHRXV
VLPXOWDQHRXV VLPXOWDQHRXV
XQWLO
Figure 7-4 Overview of configuration
7.2.3 Description of operating modes
P-manual mode
Note
The "P-manual mode" is preset for the positioner in the as-delivered condition.
The digital display of the positioner shows the current potentiometer position in the upper
line. "NOINI" blinks in the second line of the digital display.
You can move the actuator using the
decrement and increment buttons.
Switch to "Configuration" and "Initialization mode" to adapt the actuator as per the positioner.
Alarms or position feedbacks can be triggered after initializing the positioner completely.
Configuration and initialization
To get to the "Configuration" mode, press the operating mode button for at least 5 seconds
.
You can use the "Configuration" mode to adjust the positioner individually as per your
actuator and start commissioning or initialization.
The positioner reports the "Configuration" mode with a configurable fault message. A
position feedback or display of limits A1 and A2 is not possible.