Alarm, error, and system messages
11.4 Fault correction
SIPART PS2 with and without HART communications
194 Operating Instructions, 09/2007, A5E00074631-07
Fault profile (symptoms) Possible cause(s) Remedial measures
• Positioner remains in "RUN 2". • Transmission ratio selector and
parameter 2
• "YAGL" and the real stroke do not
match.
• Incorrectly set stroke on the lever.
• Piezo valve does not activate.
• Check settings: see leaflet: "Device
view (7)" picture as well as
parameters 2 and 3
• Check the stroke setting on the
lever. See table 2
• Positioner remains in "RUN 3". • Actuator actuating time is too high. • Open the restrictor completely
and/or set the pressure PZ (1) to
the highest permissible value.
• Use a booster if required.
• Positioner remains "RUN 5", does
not go up to "FINISH" (waiting time
> 5 min).
• "Gap" (play) in the positioner -
actuator - control valve system
• Part-turn actuator: check for the
firmness of the grub screw of the
coupling wheel
• Linear actuator: check for the
firmness of the lever on the
positioning shaft.
• Remove any play between the
actuator and the control valve.
Fault table 1