Alarm, error, and system messages
11.4 Fault correction
SIPART PS2 with and without HART communications
Operating Instructions, 09/2007, A5E00074631-07
195
11.4.3 Remedial measures table 2
Fault profile (symptoms) Possible cause(s) Remedial measures
"CPU test" blinks on the digital
display approximately every two
seconds.
Piezo valve does not activate.
Water in the pneumatic block (due
to wet compressed air)
In the manual and automatic
modes, the actuator cannot be
moved or can be moved only in one
direction.
Moisture in the pneumatic block
At an early stage, this fault can be
rectified with a subsequent
operating using dry air, if required,
in a temperature cabinet at 50 to
70°C.
Otherwise: repair
1)
The screw between the shrouding
cover and the pneumatic block has
not been tightened firmly or the
cover got stuck.
Tighten the screw firmly; if required,
rectify the deadlock.
Dirt (swarf, particles) in the
pneumatic block
Repair or a new device; clean
and/or replace the built-in fine
screens.
Piezo valve does not activate (a
gentle click sound is not audible
when the "+" or "-" buttons are
pressed in the manual mode.)
Deposits on the contacts between
the electronic printed circuit board
and the pneumatic block may
develop due to abrasion owing to
continuous loads resulting from
strong vibrations.
Clean all contact surfaces with
spirit; if required, bend the
pneumatic block contact springs.