Distributed Use of SIMATIC FS600 Laser Scanner in
Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 34/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
Settings of the laser scanner SIMATIC FS600
Select the laser scanner SIMATIC FS600 and double-click the line that
appears:
Then click the PROFIsafe tab.
Screenshot Note
F_Dest_Add
This value derives from the
PROPIBUS address (here: 4)
plus 500.
F_WD_Time
The default value of 10 ms is
usually too small.
A valid, current safety message
must be received from the F-CPU
during the monitoring time. Or the
DP slave will go into safe mode.