
Distributed Use of SIMATIC FS600 Laser Scanner in
Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 43/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
Network 5 and network 6
A zone pair will always become active in the safety functional example if
the following conditions are met simultaneously:
• the associated position switch (NC) switches (“0“ signal)
• the other position switch (NC) and the memory bits (dummies) all have
the “1“ signal.
During changeover (e.g. from zone pair 1 to zone pair 2) this condition is
not true for a certain duration of time. During this time the zone pair set last
remains active (e.g. zone pair 1). The following figure illustrates this.
Kommentare zu diesen Handbüchern