Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
160
C79000-G8976-C108-01
Description of the Available Statistics Counters
All elements are unsigned 16-bit counters that count the occurrences of a specific
event. The first four events are particularly important.
Counter Name Meaning
off_ts_adr_error Another station with the same name was detected.
in_ring
Indicates how often the CP entered the ring of the
active PROFIBUS master.
out_of_ring Indicates how often the CP dropped out of the ring of
the active PROFIBUS master (the CP is currently in the
ring when in_ring > out_ring).
bus_control_error
Number of bus-short circuits - These adversely affect
the functioning of the PROFIBUS and must be
eliminated.
on_double_token Indicates how often duplicate tokens or token loss was
detected.
on_timeout Indicates how often the token was lost and was
generated again by this CP.
on_syni_error Indicates how often sporadic problems occurred on the
PROFIBUS cable.
on_hsa_error Indicates how often a station address higher than the
HSA configured on this CP was detected on the bus.
off_hsa_error reserved
on_response_error Indicates how often errors occurred receiving a
response.
on_las_useless reserved
on_rec_frame_
overflow
reserved
on_fifo_error reserved
on_req_length_error reserved
off_pass_token_error
Indicates how often the token was corrupted when it
was passed on.