Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
186
C79000-G8976-C108-01
Byte 5-63
User-Specific Information
These bytes contain data with additional user-specific information. The format is
described in the slave documentation.
With the "status messages" variant
and
the "Module_Status" setting (see byte 2),
two bits are assigned to each module/slot. The module status is byte-oriented,
unused bits are set to 0.
MSB LSB
7 654321 0
Byte 5:
Module_
Status 4
Module_
Status 3
Module_
Status 2
Module_
Status 1
...
... ... ... ...
Byte m:
Module_
Status n
Module_
Status
n-1
... ...
The status bits are coded as follows:
Bit Meaning
00 Data valid
01 Data invalid: the data of the corresponding module are invalid due to
an error/fault (for example short-circuit)
10
Data invalid/wrong module: the data of the corresponding module are
invalid because the module is wrong
11 Data invalid/ no module: the data of the corresponding module are
invalid because no module is inserted