Siemens SIMATIC NET PROFIBUS Wartungshandbuch Seite 179

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 238
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 178
Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
C79000-G8976-C108-01
179
Byte 1 (Stationstatus_1)
Each bit in byte 1, the "stationstatus_1“ byte has a special meaning.
Bit Name and Meaning
7
Diag. Master_Lock
- The DP slave has already had parameters
assigned by a different master, in other words, the local master
cannot currently access this slave.
6
Diag. Prm_Fault
- This bit is set by the slave if the last parameter
assignment frame was incorrect (for example wrong length, wrong
ident number, invalid parameters).
5
Diag. Invalid_Slave_Response
- This bit is set as soon as an
implausible response is received from an addressed DP slave.
4
Diag. Not_Supported
- This bit is set as soon as a function is
requested that is not supported by the slave (for example operation in
the SYNC mode although the slave does not support this).
3
Diag. Ext_Diag
- This bit is set by the DP slave. If the bit is set, there
must be a diagnostic entry in the slave-specific diagnostic area
(Ext_Diag_Data). If the bit is not set, there may be a status message
in the slave-specific diagnostic area (Ext_Diag_Data). The meaning of
the status message must be negotiated with each specific user
program.
2
Diag. Cfg_Fault
- This bit is set when the configuration data last sent
by the master do not match those determined by the DP slave, in
other words, when there is a configuration error.
1
Diag. Station_Not_Ready
- This bit is set when the DP slave is not
yet ready for the productive phase.
0
Diag. Station_Non_Existent
- The DP master sets this bit, if the DP
slave is not obtainable on the bus. If this bit is set, the diagnostic bits
contain the status of the last diagnostic message or the initial value.
The DP slave always sets this bit to zero.
Seitenansicht 178