Using the Setup Assistant ION Setup User Guide
Page 90 © 2010 Schneider Electric. All rights reserved.
SS EvPriority: This is the Sag/Swell event priority value. This value must be greater
than the Cutoff value for Sag/Swell events to be recorded in the Event Log.
TR EvPriority: This is the Transients event priority value. This value must be
greater than the Cutoff value for Transient events to be recorded in the Event Log.
PhaseLossEnable: This allows you to enable phase loss Event Log recording and
phase loss alarming. This information can be used by MV-90 to provide phase loss
reporting.
EnergyDemand Log Screen
The EnergyDemand Log screen allows you to specify the sources for and the
interval and duration of the EnergyDemand log.
In this screen, there are two tabs:
Channels allows you to program the EnergyDemand channels.
Interval/Depth allows you to program the interval and duration of the
EnergyDemand on a specific channel.
The channels you specify in this setup screen appear in an EnergyDemand Report
that you can generate in the Reports setup screen (see “Reports Screen” on
page 104).
To specify EnergyDemand channels:
1. Click on the EnergyDemand channel that you want to specify and click Edit.
2. The Parameter Selection screen appears. The parameters are grouped by type.
Click on the + to expand the group (or click Show all available registers to see all
the registers you can select). Select the parameter and click OK.