SINAMICS G120
Inverter chassis units 0.37 kW to 132 kW (0.5 hp to 200 hp)
PM240 Power Modules
3/30
Siemens D 11.1 · 2008
3
■
Technical specifications (continued)
Line voltage
380 … 480 V 3 AC
PM240 Power Modules
Without integrated line filter 6SL3224-
0BE22-2UA0
6SL3224-
0BE23-0UA0
6SL3224-
0BE24-0UA0
6SL3224-
0BE25-5UA0
6SL3224-
0BE27-5UA0
With integrated line filter 6SL3224-
0BE22-2AA0
6SL3224-
0BE23-0AA0
6SL3224-
0BE24-0AA0
6SL3224-
0BE25-5AA0
6SL3224-
0BE27-5AA0
Output current at 400 V 3 AC
• Rated current I
rated
1)
A 5.9 7.7 10.2 18 25
• Base load current
I
L
1)
A 5.9 7.7 10.2 18 25
• Base load current
I
H
2)
A 5.9 7.7 10.2 13.2 19
•
I
max
A 11.8 15.4 20.4 26.4 38
Rated power
• based on I
L
kW (hp) 2.2 (3.0) 3 (4.0) 4 (5.0) 7.5 (10) 11 (15)
• based on
I
H
kW (hp) 2.2 (3.0) 3 (4.0) 4 (5.0) 5.5 (10) 7.5 (10)
Rated pulse frequency kHz
4 4 4 4 4
Efficiency
!
0.95 0.95 0.95 0.95 0.95
Power loss kW
0.14 0.16 0.18 0.24 0.30
Cooling air requirement m
3
/s 0.024 0.024 0.024 0.055 0.055
Sound pressure level
L
pA
(1 m)
dB
< 50 < 50 < 50 < 60 < 60
24 V DC supply
for Control Unit
A
1 1 1 1 1
Rated input current
3)
• with line reactor A 6.1 8 10.4 18.7 26
• without line reactor A
7.6 10.2 13.4 21.9 31.5
Length of cable to braking resistor,
max.
m
15 15 15 15 15
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
1 … 6 1 … 6 1 … 6 2.5 … 10 2.5 … 10
Motor connection
U2, V2, W2
Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
1 … 6 1 … 6 1 … 6 2.5 … 10 2.5 … 10
DC link connection,
connection for the braking resistor
DCP/R1, DCN, R2
Screw terminals Screw terminals Screw terminals Screw terminals Screw terminals
• Conductor cross-section mm
2
1 … 6 1 … 6 1 … 6 2.5 … 10 2.5 … 10
PE connection
On housing with
M5 screw
On housing with
M5 screw
On housing with
M5 screw
On housing with
M5 screw
On housing with
M5 screw
Motor cable length
4)
, max.
• Shielded m 50 50 50 50 50
• Unshielded m
100 100 100 100 100
Degree of protection
IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm 153 153 153 189 189
• Height mm
270 270 270 334 334
• Depth
- without Control Unit mm 165 165 165 185 185
- with Control Unit mm
230 230 230 250 250
Frame size
FSB FSB FSB FSC FSC
Weight, approx. kg
4 4 4 7 7
1)
The rated output current
I
rated
and the base load current I
L
are based on
the loading for light overload (LO).
2)
The base load current
I
H
is based on the loading for high overload (HO).
3)
The input current depends on the motor load and line impedance. The
input currents apply for a load representing the rated power (based on
I
rated
) for a line impedance corresponding to u
K
= 1 %. These current val-
ues without line reactor are quoted on the rating plate of the Power Module.
4)
Max. motor cable length 25 m (shielded) for PM240 Power Modules with
integrated line filter to maintain the limit values of EN 61800-3 Category C2.