SINAMICS G120
Inverter chassis units 0.37 kW to 132 kW (0.5 hp to 200 hp)
PM260 Power Modules
3/57
Siemens D 11.1 · 2008
3
■
Technical specifications (continued)
Line voltage
660 ... 690 V 3 AC
PM260 Power Modules
Without integrated line filter 6SL3225-0BH32-2UA0 6SL3225-0BH33-0UA0 6SL3225-0BH33-7UA0
With integrated line filter 6SL3225-0BH32-2AA0 6SL3225-0BH33-0AA0 6SL3225-0BH33-7AA0
Output current at 400 V 3 AC
• Rated current I
rated
1)
A 35 42 62
• Base load current
I
L
1)
A 35 42 62
• Base load current
I
H
2)
A 26 35 42
•
I
max
A 52 70 84
Rated power
• based on I
L
kW (hp) 30 (40) 37 (50) 55 (75)
• based on
I
H
kW (hp) 22 (30) 30 (40) 37 (50)
Rated pulse frequency kHz
16 16 16
Efficiency
!
0.95 0.95 0.95
Power loss kW
Available soon Available soon Available soon
Cooling air requirement m
3
/s 0.094 0.094 0.117
Sound pressure level
L
pA
(1 m)
dB
< 70 < 70 < 70
24 V DC power supply for the
Control Unit
A
1 1 1
Input current
• Rated current
3)
A 34 41 60
• based on
I
H
3)
A 26 34 41
Line supply connection
U1/L1, V1/L2, W1/L3
M6 screw studs M6 screw studs M6 screw studs
• Conductor cross-section mm
2
10 … 35 10 … 35 10 … 35
Motor connection
U2, V2, W2
M6 screw studs M6 screw studs M6 screw studs
• Conductor cross-section mm
2
10 … 35 10 … 35 10 … 35
PE connection
On housing with M6 screw On housing with M6 screw On housing with M6 screw
Motor cable length, max.
• Shielded m 200 200 200
• Unshielded m
300 300 300
Degree of protection
IP20 IP20 IP20
Dimensions
• Width mm 350 350 350
• Height mm
634 634 634
• Depth
- without Control Unit mm 316 316 316
- with Control Unit mm
372 372 372
Frame size
FSF FSF FSF
Weight, approx.
• without integrated filter kg 46 46 46
• with integrated filter kg
48 48 48
1)
The rated output current I
rated
and the base load current I
L
are based on
the loading for light overload (LO).
2)
The base load current
I
H
is based on the loading for high overload (HO).
3)
The input current depends on the motor load and line impedance. It
applies with a line impedance of
u
K
= 1 %. The rated input currents apply
for a load representing the rated power (based on
I
rated
) – these current
values are specified on the rating plate.