Seitenansicht 31
SINAMICS G120
Inverter chassis units 0.37 kW to 132 kW (0.5 hp to 200 hp)
PM240 Power Modules
3/32
Siemens D 11.1 · 2008
3
Technical specifications (continued)
Line voltage
380 … 480 V 3 AC
PM240 Power Modules
Without integrated line filter 6SL3224-
0BE33-7UA0
6SL3224-
0BE34-5UA0
6SL3224-
0BE35-5UA0
6SL3224-
0BE37-5UA0
6SL3224-
0BE38-8UA0
6SL3224-
0BE41-1UA0
With integrated line filter 6SL3224-
0BE33-7AA0
6SL3224-
0BE34-5AA0
6SL3224-
0BE35-5AA0
6SL3224-
0BE37-5AA0
Output current at 400 V 3 AC
• Rated current I
rated
1)
A 90 110 145 178 205 250
• Base load current
I
L
1)
A 90 110 145 178 205 250
• Base load current
I
H
2)
A 75 90 110 145 178 205
I
max
A 150 180 220 290 308 375
Rated power
• based on I
L
kW (hp) 45 (60) 55 (75) 75 (100) 90 (125) 110 (150) 132 (200)
• based on
I
H
kW (hp) 37 (50) 45 (60) 55 (75) 75 (100) 90 (125) 110 (150)
Rated pulse frequency
kHz
4 4 4 4 4 4
Efficiency
!
> 0.97 > 0.97 > 0.97 > 0.97 > 0.97 > 0.97
Power loss
kW
1.3 1.5 2 2.4 2.4 2.5
Cooling air requirement
m
3
/s 2 0.055 0.15 0.15 0.15 0.15 0.15
Sound pressure level
L
pA
(1 m)
dB < 62 < 60 < 60 < 65 < 65 < 65
24 V DC power supply
for Control Unit
A
1 1 1 1 1 1
Rated input current
3)
• with line reactor
A 94 115 151 186 210 250
• without line reactor
A
105 129 168 204 245 299
Length of cable to braking resistor,
max.
m
15 15 15 15 15 15
Line supply connection
U1/L1, V1/L2, W1/L3
M6 screw studs M8 screw studs M8 screw studs M8 screw studs M8 screw studs M8 screw studs
• Conductor cross-section
mm
2
10 … 35 1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
Motor connection
U2, V2, W2
M6 screw studs M8 screw studs M8 screw studs M8 screw studs M8 screw studs M8 screw studs
• Conductor cross-section
mm
2
10 … 35 1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
DC link connection,
connection for the braking resistor
DCP/R1, DCN, R2
M6 screw studs M8 screw studs M8 screw studs M8 screw studs M8 screw studs M8 screw studs
• Conductor cross-section
mm
2
10 … 35 1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
1 120 or
2 50
PE connection
On housing
with M6 screw
On housing
with M8 screw
On housing
with M8 screw
On housing
with M8 screw
On housing
with M8 screw
On housing
with M8 screw
Motor cable length
4)
, max.
• Shielded
m 50 50 50 50 50 50
• Unshielded
m
100 100 100 100 100 100
Degree of protection
IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width
mm 275 350 350 350 350 350
• Height
- without integrated filter
mm 499 634 634 634 634 634
- with integrated filter
mm
635 934 934 934
• Depth
- without Control Unit
mm 204 316 316 316 316 316
- with Control Unit
mm
260 372 372 372 372 372
Frame size
FSE FSF FSF FSF FSF FSF
Weight, approx.
• without integrated filter
kg 16 36 36 36 39 39
• with integrated filter
kg
23 52 52 52
1
)
The rated output current I
rated
and the base load current I
L
are based on
the loading for light overload (LO).
2)
The base load current
I
H
is based on the loading for high overload (HO).
3
)
The input current depends on the motor load and line impedance. The input
currents apply for a load representing the rated power (based on
I
rated
) for a line impedance corresponding to u
K
= 1 %. These current values
without line reactor are quoted on the rating plate of the Power Module.
4)
Max. motor cable length 25 m (shielded) for PM240 Power Modules with
integrated line filter to maintain the limit values of EN 61800-3 Category C2.
© Siemens AG 2008
Seitenansicht 31