Screw terminal 1
Spring-loaded terminal 2
3UG4 monitoring relays – for residual-current monitoring
17
3UL22 summation current transformer for external ground fault monitoring
Rated Rated residual Through hole For Protodur cable Order No.
insulation current I
n
diameter (for through-
voltage U
i
connection)
Detection of residual currents in machines and systems
690 V AC 0.3 A 40 mm max. 4 x 95 mm
2
3UL2201-1A
0.5 A 3UL2201-2A
1 A 3UL2201-3A
690 V AC 0.3 A 65 mm max. 4 x 240 mm
2
3UL2202-1A
0.5 A 3UL2202-2A
1 A 3UL2202-3A
10 A 3UL2202-2B
16 A 3UL2202-3B
25 A 3UL2202-4B
40 A 3UL2202-5B
1000 V AC 0.3 A 120 mm max. 8 x 300 mm
2
3UL2203-1A
0.5 A 3UL2203-2A
1 A 3UL2203-3A
6 A 3UL2203-1B
10 A 3UL2203-2B
10 | 11
Monitoring Relays
Display range Setting ranges Contacts Hysteresis Hysteresis ON delay Tripping Rated control Order No.
for warning and with treshold with warning delay time supply voltage
disconnection value value
Width 22.5 mm, digitally adjustable featuring LCD display, connectable fault memory,
monitoring of warning threshold and limit value exceedance, for 3UL22 summation current transformer with I
n
from 0.3 to 40 A
10 to 120% 10 to 100% 1 CO +
Display accuracy
5% fixed of 0.1–20.0 s 0.1–20.0 s 90–690 V AC 3UG4624- CS20
of the nominal of the nominal 1 CO of up to 50% of
the nominal
transformer transformer
the nominal trans-
transformer
value in A value in A
former value in A value in A
NEW!