Siemens EF6 Series Bedienungsanleitung Seite 19

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 32
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 18
Screw terminal 1
Spring-loaded terminal
2
11
3RS10/3RS11 Temperature Monitoring Relays
Sensor Measuring range Rated control supply Order No.
(measuring range limit voltage V
s
depends on the sensor) 50–60 Hz AC
“Temperature monitor” acc. to DIN 3440, digitally adjustable, 2 threshold values, 45 mm wide; 1 CO + 1 CO + 1 NO,
memory function can be enabled using an external jumper. Relay parameters have a holding on supply failure function
–50...+500 °C 24 V AC/DC 3RS10 40- GD50
24–240 V AC/DC 3RS10 40- GW50
–50...+932 °F 24 V AC/DC 3RS20 40- GD50
24–240 V AC/DC 3RS20 40- GW50
–99...+999 °C 24 V AC/DC 3RS11 40- GD60
24–240 V AC/DC 3RS11 40- GW60
–99...+1830 °F 24 V AC/DC 3RS21 40- GD60
24–240 V AC/DC 3RS21 40- GW60
“Temperature limiter” and “temperature monitor” acc. to DIN 3440, digitally adjustable, 2 threshold values, 45 mm wide;
1 CO + 1 CO + 1 NO, tripped state and relay parameters are saved using a holding on supply failure function
–50...+750 °C 24 V AC/DC 3RS10 42- GD70
24–240 V AC/DC 3RS10 42- GW70
–99...+1800 °C 24 V AC/DC 3RS11 42- GD80
24–240 V AC/DC 3RS11 42- GW80
Motor monitoring relays, digitally adjustable for up to 3 sensors, 45 mm wide; 1 CO + 1 CO + 1 NO
Sensor No of Measuring range Rated control supply
sensors voltage V
s
Order No.
1 to 3 –50...+500 °C 24–240 V AC/DC 3RS10 41- GW50
sensors –50...+932 °F 24–240 V AC/DC 3RS20 41- GW50
1)
NTC type: B57227-K333-A1 (100 °C: 1.8 k; 25 °C: 32.762 k)
18 | 19
Monitoring Relays
PT100/1000;
KTY83/84;
NTC (resistance sensor)
1)
PT100/1000;
KTY83/84;
NTC (resistance sensor)
1)
TYPE J, K, T, E, N
(thermoelement)
PT100/1000;
KTY83/84;
NTC (resistance sensor)
1)
TYPE J, K, T, E, N, R, S, B
(thermoelement)
Digitally adjustable evaluation units
Temperature monitoring relays distinguish themselves
due to the fact that they are extremely easy to operate.
The actual temperature is always displayed on the three-
digit LED display. A dedicated relay with one NO contact
is integrated to monitor the sensor.
The relay is switched-off in the parameterizing mode.
The following parameters can be set:
Sensor type
2 threshold values J
1
, J
2
1 hysteresis; this acts on both thresholds (099 K)
1 delay time; this acts on both thresholds (0 999 s)
Either the open-circuit/closed-circuit principle can be
selected
Function: Overtemperature/Undertemperature
(overrange/underrange) or window monitoring within
a defined range
Versions with a wide-range voltage have electrical
isolation.
The temperature ranges are dependant on the sensor
type (refer to the function).
The short-circuit and wire breakage detection, as well as the
measuring range are restricted, depending on the sensor type:
Measuring ranges in °C for thermoelements
Sensor Short Wire 3RS11 40 3RS11 42
type circuit breakage
measuring range
measuring range
J x –99...999 –99...1200
K x –99...999 –99...1350
T x –99...400 –99...400
E x –99...999 –99...999
N – x –99...999 –99...999
S – x 0...1750
R – x 0...1750
B – x 400...1800
Measuring ranges in °C for resistance sensors
Sensor Short Wire 3RS10 40 3RS10 42
type circuit breakage
measuring range
measuring range
PT100 x x –50...500 –50...750
PT1000 x x –50...500 –50...500
KTY83-110 x x –50...175 –50...175
KTY84 x x –40...300 –40...300
NTC
1)
x – 80...160 80...160
1)
NTC type: B57227-K333-A1 (100 °C: 1.8 kΩ; 25 °C: 32.762 kΩ)
Under www.siemens.com/temperature,
you will find the right sensor.
Seitenansicht 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24 ... 31 32

Kommentare zu diesen Handbüchern