Screw terminal 1
Spring-loaded terminal
2
3UG4 monitoring relays – single-phase current monitoring
Measuring range Hysteresis Contacts Starting- Tripping Control supply voltage Order No.
bypass time delay
22.5 mm wide, all of the devices can be digitally set and have an LCD display, a fault memory that can be switched-in,
simultaneous monitoring for overcurrent and undercurrent over the complete measuring range
3.0 mA AC/DC 0.1 mA–250 mA 1 CO 0.1–20 s 0.1–20 s 24 V AC/DC 3UG4621- AA30
up to 500 mA AC/DC 24–240 V AC/DC 3UG4621- AW30
0.05 A AC/DC 0.01 A–5 A 1 CO 0.1–20 s 0.1–20 s 24 V AC/DC 3UG4622- AA30
up to 10 A AC/DC 24–240 V AC/DC 3UG4622- AW30
17
Power factor and active current monitoring
Measuring range Measuring range
Power factor Active current On delay Tripping delay Rated control Order No.
for power for active hysteresis hysteresis supply voltage
factor current I
res
22.5 mm wide, all of the devices can be digitally set and have an LCD display, a fault memory that can be switched-in,
simultaneous power factor and active current monitoring over the entire measuring range
0.1–0.99 (cos ) 0.2–10.0 A 0.1 (cos ) 0.1–2.0 A 0–99 s 0.1–20.0 s 90–690 V AC
3UG4641- CS20
Monitoring Relays
Current and cos as a function of the motor load
Monitoring Plant/system states
parameter
Current • Overload monitoring
monitoring • Underload monitoring close to the rated torque
• Monitoring the functionality of electric loads
• Wire breakage monitoring
• Energy management
(phase current monitoring)
• Threshold value switch for analog signals
up to 20 mA
Power factor and • No-load monitoring
active current • Underload monitoring in the
monitoring lower power range
• Overload monitoring
• Extremely simple power factor
monitoring of
line supplies to control compensation equipment
• Energy management
• Interrupted cable between the cabinet
and the motor
Rule of thumb:
cos changes
significantly below
the rated load;
the current increases
overproportionally
above the rated load.
The I
res
active current shows a linear correlation between the motor load
and the measured value over the entire measuring range.
170
Rated load
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160
I
x cos
cos
I
28
21
14
7
0
A
Motor load
cos
8 | 9