Network Installation
2-9
TIWAY I Gateway User Manual
100
80
100
max
30
30
Double Drop
Drop
lines less
than 36 inches
can be ignored.
100
50min
I000000
36
max
Figure 2-6 Additional
T
ap Spacing Rules
If a tap cable is installed
less than the minimum
distance as stated in the
primary rule, then the two drops, the previous one and the one being
installed, are considered a
double
drop
.
Double
drops are allowed, but triple drops are not allowed.
After installing a double drop, the next tap must be placed at the minimum
distance or farther
. In this case, the minimum distance would be one half
the distance of the longest of the two tap lines making up the double drop.
Drops that have a tap line that is
less than 36 inches
can be ignored in
calculating the minimum distance between taps.
There is no limit to the number of drop stations that can be connected to the
same tap line.
Each station must have its own tap, and the overall drop line length cannot
exceed 100 feet. The cable used to attach each station to the drop line
cannot
exceed the 36-inch maximum.
Double Dr
ops
Short Dr
ops
Multidr
op T
aps