Modbus Commands
C-4
TIWAY I Gateway User Manual
Modbus Protocol Overview (continued)
The
Gateway ignores messages that contain invalid characters. Messages
containing the following errors will also be ignored.
Incorrect checksum
Parity error
Framing errors
Incomplete transmission
This section outlines some of the differences between Modbus and TIW
AY I
network commands.
Whereas Modbus uses
Functions Codes, TIW
A
Y I uses
Primitives.
Primitives differ from Function codes in one important way: primitives
use TT
-types to allow one primitive to address different types of data.
W
ith Modbus a different function code is required for each type of data.
For all SIMA
TIC TI Series 505 PLCs, the first address for each type of
memory is always 1. Modbus PLCs by comparison allow 0 as the first
legal address.
If each system were to return one byte (8 bits) representing eight
discrete coils, they would each be positioned as shown in Figure C-2.
8
I000000
7654321 87654321
Coil
No.
Coil No.
Modbus PLCs SIMATIC TI PLCs
MSB LSB<
< <
MSB LSB
< < <
Figur
e C-2
Bit
Orientation
Invalid Characters
and Messages
Modbus Functions