Gateway Installation and Configuration
3-4
TIWAY I Gateway User Manual
Installing the TIWAY I Gateway (continued)
6. Run
the user
-initiated test. (Refer to the Diagnostics T
ests section.)
7.
Remove loopback connector
.
8.
Set the Online/Offline switch on the Gateway to the ONLINE position.
9.
Connect the Local Line or RS-232 interface cable to the TIW
A
Y I port.
10.
Connect the host system interface cable to to the host port.
11.
Configure the communications parameters on the host system. Make
sure that the host system baud rate matches the rate you plan to set on
the Gateway
.
12.
Set the dipswitches on the Gateway
. Be sure to set the parity
, duplex,
and synchronous/asynchronous selections to match the corresponding
settings on the host system. (See Figure 3-3 and Section 3.2.)
13.
Check to see that the GA
TEWA
Y GOOD, TRANSMIT
, and RECEIVE
indicators on the Gateway are on, and that TEST is flashing.
14.
Configure the data and status registers in the variable memory of the
PLCs on the TIW
A
Y I network. (Refer to the appropriate PLC manuals
for more information if necessary
.)
15.
Press the RESET button on the Gateway
.
16.
Begin program execution.